Serviceportal Industrie

Power Plant Construction

Pipe Shoes

Typen Z
Typ L

Guiding Bracket FW F L/Z


Group

A705


view as PDF file

Application

Using this Guiding Bracket it's possible to guide Pipe Shoes with different plate thicknesses. The different versions of Type Z are suitable for the respective specified maximum plate thickness (t)and so additionally allow the absorption of lifting forces.

Scope of delivery

Delivery as set comprising 2 Guiding Brackets.

Installation

Installation on top of Beam Section TP F 80 repectively F 100 with 2 Self Forming Screws FLS F per Guiding Bracket, i.e. per set 4 Self Forming Screws have to be used altogether. You can find the Self Forming Screw in the siFramo chapters (section Siconnect).

There are 3 mm of free play in the vertical z-axis for Type Z.
There are 3 mm of free play in the vertical y-axis for all Types.

Technical Data

Type
perm. load Fy
[kN]
perm. torque via Fy*
[kNm]
perm. load Fz
[kN]
FW F 80, all Types Z 1.9 0.4 5.0
FW F 80, Typ L 1.9 - -
FW F 100, all Types Z 1.9 0.4 6.4
FW F 100, Typ L 1.9 - -


* the torque is calculated by M = Fy x h, whereas the perm. load for Fy may not be exceeded. Dimension h refers from the middle of the pipe to the top of the base plate.
The perm. loads have been determined by load tests following DIN EN 13480-3 annex J.
The used Pipe Shoe has to be verified separately.

Material:
Steel, HCP

Approvals / Compliance


* suitable for Sikla Pipe Shoes

Type t
[mm]
W
[kg]
Qty.
[set]
Part-
No.
FW F 80 Z 6 6 0.5 25 113628
FW F 80 Z 9 9 0.5 25 113629
FW F 80 Z 12 * 12 0.5 25 113630
FW F 80 Z 15 15 0.5 25 113975
FW F 80 L - 0.5 25 113627
FW F 100 Z 6 6 0.6 25 113632
FW F 100 Z 9 9 0.6 25 113633
FW F 100 Z 12 * 12 0.6 25 113634
FW F 100 Z 15 15 0.6 25 113976
FW F 100 L - 0.6 25 113631